Fan-Filter Module FFM-E
Product Description
The fan-filter modules, made by COLANDIS®, are complete modules, consisting of a housing made of brushed stainless steel, the filter medium (HEPA-filter), and the corresponding fan technology. Optionally, pre-filter, speed control and pressure monitoring can be integrated.
The fan-filter modules are used to generate particle-poor environments in clean rooms, in devices and facilities. They are perfectly suited to be used to create turbulent mixed airflow as well as to create unilateral flows. The installation position of the fan-filter modules is arbitrary. They can be used at ambient temperatures from -15 to +40 ° C (without condensation) at a maximum relative humidity of 80%.
Technical Data
- Housing and fan plate made of brushed stainless steel
- HEPA filters with efficiency of 99,995 % @MPPS
(filter class H14 according to EN 1822) - Handle protection on suction and clean air side
- Fans in AC or EC version
- Operating voltage 230V 50/60 Hz
Connection via IEC socket on the top of FFM-E
Standard Sizes
| FFM-E | Filter | Volume flow | Air speed | |||
|---|---|---|---|---|---|---|
| Widht | Depth | Height | Widht | Depth | max. [m³/h] | max. [m/s] |
| 464 | 312 | 250 | 457 | 305 | 330 | 0,75 |
| 617 | 312 | 250 | 610 | 305 | 380 | 0,64 |
| 769 | 312 | 250 | 762 | 305 | 410 | 0,55 |
| 922 | 312 | 250 | 915 | 305 | 680 | 0,75 |
| 464 | 464 | 250 | 457 | 457 | 400 | 0,59 |
| 617 | 464 | 350 | 610 | 457 | 650 | 0,71 |
| 769 | 464 | 350 | 762 | 457 | 650 | 0,57 |
| 922 | 464 | 350 | 915 | 457 | 850 | 0,61 |
| 1227 | 464 | 350 | 1220 | 457 | 960 | 0,51 |
| 617 | 617 | 350 | 610 | 610 | 780 | 0,63 |
| 769 | 617 | 350 | 762 | 610 | 900 | 0,58 |
| 922 | 617 | 350 | 915 | 610 | 950 | 0,51 |
| 1227 | 617 | 350 | 1220 | 610 | 1560 | 0,62 |
| 769 | 769 | 350 | 762 | 762 | 970 | 0,49 |
| 922 | 769 | 350 | 915 | 762 | 1560 | 0,66 |
Our fan filter modules are available in all standard filter sizes. Other dimensions on request.
Options
- Housing and fan plate powder paint coated
(Color can be chosen) - alternatively: ULPA filters or PTFE filters
- alternativly: 115V/50Hz or wide-range voltage
- integrated or external speed control for setting an optimal air flow
- integrated pressure monitoring
- Different pre-filters (note the extra height)
- Transportation grips and/or mechanical interfaces for mounting